The temperature and pressure reducer is to reduce the high temperature and high pressure steam to the low pressure and low temperature steam that the customer can use. It can be divided into 1, integrated temperature reducing and pressure reducing device, the temperature reduction and pressure reduction are carried out in the same temperature reduction and pressure reducing valve 2. Split type temperature reduction and pressure reducing device, the temperature reduction and pressure reduction are carried out separately, and the pressure reduction adopts separate pressure reduction The valve has the advantages of split temperature and pressure reducer, high control accuracy, stable operation, sensitive adjustment, and can effectively eliminate the effect of static difference. These two types of temperature and pressure reducers are electric power, petrochemical, light industry, textile printing and dyeing, and medicine. It is a kind of temperature reduction and pressure reduction equipment widely used in industries such as cogeneration, etc. The following aspects should be paid attention to when installing and using:
The temperature and pressure reducing valve and the water supply regulating valve must be installed vertically so that the center of gravity is down and there is enough space around it to facilitate the disassembly and maintenance of the valve. The flow direction of the medium is indicated by the arrow on the valve body, and debugging is carried out according to the manual of the electric actuator.
There should be a straight pipe induction length at the inlet of the temperature reducing valve, the inlet straight pipe section is ≥5DN and not less than 2m, and the outlet straight pipe section should have a slope of 1~5% downstream.
The installation position of the feed water regulating valve should not be far away from the temperature and pressure reducing valve, and slightly lower than the water inlet of the temperature and pressure reducing valve.
After the valve is installed, the piping system should be cleaned to thoroughly remove all kinds of impurities in the pipe, such as oxide scale, welding slag, etc. In order to prevent impurities from damaging the inside of the valve during cleaning, protective measures must be taken. The plug-in of the valve seat can be protected or the pipeline can be flushed before connecting with the valve.
The valve sealing packing is flexible graphite, which has good expansion performance after being heated, so it should not be too tightly pressed when it is cold. When replacing the packing, pay attention to avoid damaging the surface of the valve stem.
A fixed bracket shall be installed under the safety valve on the steam pipeline, and a movable bracket shall be installed at the end of the temperature and pressure reducing valve and the steam pipeline.
A steam trap should be installed at the lowest point of the steam inlet pipeline, and a temperature compensator should be installed when the steam inlet and outlet are connected to the device.
The large hangers, safety valve exhaust pipes, steam traps, compensators, installation pipelines, measuring elements, and connectors of the thermal adjustment device required by this device are all taken care of by the user. The main thermal adjustment device is supplied according to the order contract agreement. Regulations.
All pipes with a diameter less than φ57mm are supplied as straight pipes, which are bent and welded on site during installation.
After installation, remove the valve of the pressure reducing system and the water supply system, and blow the entire pipeline to remove the welding slag, welding nugget and other dirt in the pipeline, and then install the dismantled valve when there is no debris. The valve is simultaneously then subjected to a hydrostatic test. The test pressure is 1.5 times of the pressure of the workpiece. When the test pressure is used, the safety valve must be removed, sealed with a blank plate, and then pressurized for 5 minutes. Check that there is no leakage at all connections.