What Is The Principle Of Temperature Reduction And Pressure Reduction Device?

Oct 29, 2022 Leave a message

Desuperheating and decompression device is a steam thermal parameter widely used in thermal industry in modern industry, such as cogeneration, central heating (or steam supply) and light industry, electric power, chemical industry, textile and other enterprises. So, what is the principle of desuperheating and decompression device?


1. Cooling system: The cooling water is sprayed from different nozzles into the steam in the Venturi tube or steam pipeline through the high pressure difference regulating valve (or variable frequency water pump, etc.) to reduce the steam temperature.


2. Decompression system: It consists of a pressure reducing valve and a throttle orifice. The pressure reducing valve can adjust the pressure by changing the flow area.


3. Cooling and decompression system: The cooling and decompression system is combined into one, which reduces the overall size of the device and increases the technical complexity.


4. In order to prevent the secondary steam pressure from exceeding the specified value, the safety system of the cooling and decompression device: automatically open the safety valve and discharge the excess steam, so as to achieve the role of decompression and safety protection. Due to different parameters, there are the following structural forms, our factory chooses a spring safety valve pulse in the design

Flush and main safety valve (one or more) equipped with lever type safety valve


5. The thermal control system of the desuperheating and decompression device is an important device for adjusting the parameters of the steam outlet. It receives the outlet temperature and pressure signals, and after information processing, commands the actuator to stabilize the outlet parameters (temperature and pressure) within the range required by the user, and realize automatic adjustment.


What kinds of desuperheating and decompression devices can be classified according to inlet pressure and temperature?


1. Medium temperature and medium pressure decompression and decompression device:

Primary steam parameters (inlet steam parameters): pressure P1=3.9 MPa; T1=450 pressure;

The pressure P2 of the secondary steam parameters (outlet steam parameters) is determined by the user's requirements; T2=saturation temperature;

Flow: Q=2*360+ton/hour(ton/hour)


2. Sub-high pressure desuperheating and decompression device:

Primary steam parameters (inlet steam parameters): pressure P1=5.4 ]Pa; T1=485 pressure;

The pressure P2 of the secondary steam parameters (outlet steam parameters) is determined by the user's requirements; T2=saturation temperature;

Flow: Q=20^ 200t/hour (ton/hour)


3. High temperature and high pressure decompression and decompression device:

Primary steam parameters (inlet steam parameters): pressure P1=10 MPa; T1=540 pressure;

The pressure P2 of the secondary steam parameters (outlet steam parameters) is determined by the user's requirements; T2=saturation temperature;

Flow: Q=30' 240t/h (ton/h)