Steam control valve
The steam control valve integrates a steam pressure reducing control valve and a set of cooling systems into a set of equipment. The steam pressure and flow are controlled by the cock in the steam control valve, and the cooling water injection rate or the corresponding steam temperature is adjusted by the flow control valve.
working principle
In the throttling process of the control valve, the pressure can be converted into kinetic energy, that is, the pressure of the medium (in this case, steam) decreases, but the flow rate increases. The peak of the steam flow rate appears between the valve seat and the cock, and is usually called the "flow neck (contracted section)". The steam control valve uses a high-speed steam flow in the neck to produce the smallest droplets.
The most common structure of steam control valve does not exceed two. The first is to install a traditional injection system at the outlet of the steam pressure control valve. The injection system sprays the cooling water as close as possible to the flow neck through the cock shaft of the steam pressure control valve. Or the high-pressure atomized steam is guided to the outlet of the steam pressure control valve through a separate pipe to form a steam pressure difference at the outlet, so that cooling water is injected into the steam flow after atomization.
Steam control valve
The design of the steam control valve is very unique. It directly injects cooling water into the outlet end of the flow neck, so that the cooling water enters a special device called a diverter. The structure of the shunt includes inner and outer metal cages and built-in wire mesh. Under the action of the diverter, the steam at the highest flow rate will contact the cooling water at the inner edge of the diverter. This helps to achieve a very high Weber value, in other words an excellent water atomization effect. After the extremely tiny water droplets pass through the built-in screen of the diverter, the diameter is further reduced.
Not only that, the flow rate of steam in the flow neck area is not related to the steam flow rate, so the Samson steam control valve can achieve the maximum steam and water regulation ratio. The only limiting effect on the turndown ratio is the pipeline flow rate. The diverter can also serve as an additional steam pressure attenuator, which means that the internal sound pressure and system vibration are reduced to a minimum.
The steam-water mixture is sprayed from the flow divider in a mist state, and the remaining water droplets have a very small diameter, so the evaporation time can be shortened to a minimum, and the water can be evenly spread across the flow channel section of the steam flow. This makes the outlet temperature of the system very close to the saturation temperature.
In order to avoid thermal stress caused by cooling water and superheated steam, cooling water is injected into the valve through a built-in sleeve, and the sleeve and the valve body will not directly contact. This design can prevent the water pipe flange joint from being subjected to thermal stress. In addition, the water mist sprayed by the diverter is very fine, eliminating the possibility of large-diameter water droplets contacting the valve body or the downstream pipe wall.